10302/2/1 Honeywell Watchdog Repeater (WDR)
The 10302/2/1 is a Watchdog Repeater from Honeywell. It serves multi-PSU systems with 24 Vdc to 5 Vdc supplies. Moreover, it generates the watchdog output for each added PSU. It also monitors 5 Vdc when no other monitor exists. Use it with M24-20 HE or M24-12 HE supplies. In addition, it is needed when supply voltages can exceed 31.0 Vdc. In that case, the maximum output must stay below 37 Vdc under single or double fault. The unit handles watchdog current above 900 mA. Furthermore, it supports mixed redundant and non-redundant I/O. It also works with redundant Central Parts plus non-redundant I/O.
Key Technical Data
- Manufacturer: Honeywell
- Product No: 10302/2/1
- Type number: 10302/2/1 12600
- Product type: Watchdog repeater (WDR)
- Approvals: CE, TÜV, UL
- Software versions: ≥ 3.00
- Space: 4 TE, 3 HE (4 HP, 3U)
- 5 Vdc draw: 35 mA without WDROUT current
- 24 Vdc draw: 25 mA
- WDG1 + WDG2 input: 0.1 mA
- Module code: holes A5, A9
- Rack code: large pins A5, A9
- Weight: 0.12 Kg
FAQ
Q: When is a watchdog repeater required?
A: Add one for each extra 24 Vdc to 5 Vdc PSU. Also add it when 24 Vdc comes from M24-20 HE or M24-12 HE. It is also needed if supply voltage can exceed 31.0 Vdc.
Q: What is the maximum allowed 24 Vdc output?
A: Stay below 37 Vdc. This limit applies under any single or double fault in the power supply unit.
Q: Can it handle high watchdog current?
A: Yes. Use the 10302/2/1 when watchdog current exceeds 900 mA.
Q: Does it fit mixed redundant and non-redundant I/O?
A: Yes. It creates the watchdog output for output modules in the non-redundant I/O part.
Q: How do I verify a used unit?
A: Check the 5 Vdc draw at 35 mA and the 24 Vdc draw at 25 mA. Also test WDG1 and WDG2 input at 0.1 mA.
Q: My rack uses large pins A5 and A9. Is this compatible?
A: Yes. The module code uses holes A5 and A9. The rack code uses large pins A5 and A9.