1762-L40AWAR | Allen-Bradley | MicroLogix 1200 PLC with 24 AC Inputs and 16 Relay Outputs
The 1762-L40AWAR is an Allen-Bradley MicroLogix 1200 Programmable Logic Controller. It runs on 120 to 240 VAC supply. It has 24 AC inputs and 16 relay outputs. Relay contacts are rated 24-125 VDC and 120-240 VAC, with a 20,000,000 cycle mechanical life. One 8-pin mini-DIN port supports RS232 DF1, plus a dedicated programming port. Both ports speak DF1, DH-485, ASCII, and Modbus. The unit controls loads up to 1440 VA. It fits panel builders and plants that need a compact all-in-one controller for AC field devices.
Technical Data
- Manufacturer: Rockwell Automation
- Brand: Allen-Bradley
- Catalog Number: 1762-L40AWAR
- Series: MicroLogix 1200
- Power supply: 120 to 240 Volts AC
- Inputs: 24 sink/source, 120V AC circuit type
- Outputs: 16 relay, volt-free contacts
- Relay contact rating: 24-125 VDC and 120-240 VAC
- Mechanical cycles: 20,000,000
- Load current: 10A minimum
- Communication ports: One 8-pin mini-DIN serial, one programming port
- Supported protocols: DF1, DH-485, ASCII, MODBUS
- Power supply usage: 82 VA
- Inrush current: 120V ac 25A for 8 ms; 240V ac 40A for 4 ms
- Dimensions: Height 90 mm (104 mm with DIN latch open), Width 160 mm, Depth 87 mm
- Shipping weight: 2.4 pounds
- Ambient operating temperature: 0 to 55°C
- UPC: 10781180463867
Supply and Warranty Terms
- 12-month warranty on this controller.
- Dispatch in 24 to 28 hours.
- Shipping by FedEx, UPS, and DHL.
- Each unit is checked before packing.
FAQ
Q: Can the 1762-L40AWAR talk to power meters without a gateway?
A: Yes. The serial port supports Modbus master/slave. Point it at meters that speak Modbus RTU over RS232. Set baud, parity, and node address to match the meter. Use a shielded cable and keep runs short. This saves the cost of a protocol converter.
Q: My sensors pull low current. Will they read correctly on these inputs?
A: Check the OFF state leakage first. This unit produces at least 1.5 mA of OFF leakage. A two-wire sensor that stays on below that level can read as ON. Add a bleeder resistor or choose a sensor rated to sink more than 1.5 mA. Test one channel before you wire the full panel.
Q: What should I confirm before ordering a spare 1762-L40AWAR?
A: Check three things. First, your supply is 120-240 VAC. Second, your I/O count fits 24 inputs and 16 relay outputs. Third, your loads stay inside 1440 VA total. Send us your rack photo and wiring drawing. We verify the fit before shipment.
Q: Can I drive both 120V AC and 24V DC loads from the relay outputs?
A: Yes. Contacts are rated 24-125 VDC and 120-240 VAC. Keep each load within the contact rating and the 10A load current. Group wiring by voltage to reduce noise. Do not mix AC and DC on the same terminal block.
Q: How do you handle shipping and warranty on this unit?
A: We dispatch in 24 to 28 hours. We ship by FedEx, UPS, or DHL. Every controller carries a 12-month warranty. We test each unit before it leaves our warehouse. You can reach us at info@oiltechcontrols.com for order questions.