1766-L32BWAA Allen-Bradley MicroLogix 1400 Controller
The 1766-L32BWAA is a MicroLogix 1400 programmable logic controller in the Bulletin 1766 family. It packs 38 I/O points, three communication ports, and a backlit LCD into one compact unit. Engineers pick the 1766-L32BWAA for mixed AC input and relay output panels that also need Ethernet and serial links. Core value: one controller covers discrete logic, analog signals, network messaging, and local status display.
Technical Specifications
- Brand: Allen-Bradley, Rockwell Automation
- Model / Catalog No.: 1766-L32BWAA
- Series: MicroLogix 1400, Bulletin 1766
- I/O count: 38 points total
- Digital inputs: 12 fast 24V DC plus 8 normal 24V DC
- Relay outputs: 12
- Analog I/O: 4 inputs and 2 outputs, 0-10V DC, 12-bit
- Input power: 110 to 240V AC, 47-63 Hz
- Power consumption: 120 VA
- Inrush current: 25A at 120V AC for 8 ms; 40A at 240V AC for 4 ms
- Memory: 20 KB, 10 KB user program plus 10 KB data, battery-backed RAM
- Communication ports: combo RS232/RS485 isolated, isolated RS232, Ethernet
- Serial protocols: DF1, ASCII, Modbus RTU, DNP3, DH485
- Ethernet protocols: EtherNet/IP, DNP3 over IP, Modbus TCP/IP
- High-speed counters: up to 6 embedded, 100 kHz
- Features: built-in RTC, backlit LCD, trim potentiometers, web server, email
- Expansion: up to 7 x 1762 I/O modules
- Mounting: DIN rail or panel
- Dimensions: 3.5 x 7.08 x 3.43 in
- Weight: 2 lb
- Certifications: UL, c-UL, CE
Installation Notes
- Use a clean, dry panel with Over-Voltage Category II circuits or lower.
- Feed 110-240V AC to the supply terminals and keep wiring away from analog lines.
- Fit the unit on DIN rail or bolt it to a panel with the open enclosure.
- Plan for 7 expansion modules and reserve rail space.
- Ground the chassis before power-up to reduce noise on analog inputs.
Commissioning and Diagnostics
- Read controller and I/O status on the backlit LCD during first power-up.
- Set network parameters through the LCD or the web server.
- Trim potentiometers simulate registers for analog tests.
- Use the real-time clock for time-stamped events and scheduled control.
- Watch for inrush peaks on shared 120V AC circuits during startup.
- Check Ethernet link LEDs and serial port activity when a protocol fails.
Compatibility and Fit
- Works with the 1762 expansion I/O family for extra points.
- Suits panels built around 24V DC sensors and 120V AC field devices.
- Fits retrofit jobs that replace older MicroLogix controllers.
- Good match for conveyors, mixers, pumps, and packaging lines.
- Fits water treatment, material handling, and OEM machine builds.
Oiltech Controls Review
- 15+ years of industrial automation spare parts experience.
- Global shipment support with FedEx, UPS, and DHL.
- Tested industrial surplus and refurbished options.
- Technical verification before shipment on every order.
- Support for obsolete control systems and legacy MicroLogix lines.
- 12-month warranty and 24-28 hour dispatch on stocked units.
- Contact: info@oiltechcontrols.com or WhatsApp +86 158 8020 0923
FAQ
- How many I/O points does the 1766-L32BWAA offer?
It provides 38 points: 20 digital inputs, 12 relay outputs, and 6 analog channels. - Can the 1766-L32BWAA run a DNP3 network?
Yes. DNP3 works over serial ports and over Ethernet as DNP3 over IP. - What should I check before buying a used MicroLogix 1400?
Ask for the firmware revision, LCD condition, and port test results. Request a photo of the nameplate to confirm the catalog number. - Does this controller support analog control without extra modules?
Yes. It has 4 analog inputs and 2 analog outputs at 12-bit, all 0-10V DC. - How do I choose between this model and a higher I/O controller?
Pick this model when 38 points and 7 expansions are enough. Move up when you need more memory or faster scan times.
Copyright © 2026 Oiltech Controls Limited. https://www.oiltechcontrols.com/ All rights reserved.
All rights reserved.










Reviews
There are no reviews yet.