6ES7332-5HB01-0AB0 Analog Output SM 332 – 2 AO, Isolated
Series: SIMATIC S7-300 | Type: Analog Output Module | Part Number: 6ES7332-5HB01-0AB0
Isolated analog output module with 2 channels for voltage or current signals. 11/12-bit resolution, short-circuit protected, and supports hot swapping. Ideal for precise actuator control in industrial automation.
Core Technical Specifications
- Supply voltage: 24 V DC (rated), reverse polarity protected
- Power loss: typ. 3 W
- Analog outputs: 2 isolated channels, configurable as voltage or current
- Voltage ranges: 0..10 V, 1..5 V, ±10 V
- Current ranges: 0..20 mA, ±20 mA, 4..20 mA
- Resolution: 12 bit (0..10 V, 0..20 mA) / 11 bit + sign (±10 V, ±20 mA)
- Conversion time: 0.8 ms per channel
- Load impedance: voltage output ≥1 kΩ; current output ≤500 Ω
- Cable length (shielded): max. 200 m
Accuracy & Error Limits
- Operational error limit (full temp. range): ±0.5 % (voltage), ±0.6 % (current)
- Basic error limit (at 25 °C): ±0.4 % (voltage), ±0.5 % (current)
- Settling time: resistive 0.2 ms, capacitive 3.3 ms, inductive 0.5 ms (1 mH) .. 3.3 ms (10 mH)
Diagnostics & Status
- Diagnostics: parameterizable, readable via SF LED (red group error)
- Alarms: diagnostic alarm configurable
- Potential isolation: between channels and backplane bus (500 V DC test)
Suitable Equipment & Applications
- SIMATIC S7-300 PLC systems (CPU 31x, 41x series)
- ET 200M distributed I/O stations
- Analog signal conditioning for variable speed drives (VSD)
- Proportional valve control in hydraulic/pneumatic systems
- Temperature setpoint output for PID controllers
5 Professional FAQs – Selection & Experience
- Question: Can I mix voltage and current outputs on this module?
Answer: Yes, each channel is independently configurable. However, we advise setting both to the same type for easier wiring and spare stocking. - Question: What is the maximum cable length for 4..20 mA?
Answer: Shielded cable up to 200 m is acceptable. For longer runs, use a signal isolator or active repeater – we have seen many field issues due to excessive cable length. - Question: Is this module hot-swappable?
Answer: Yes, it supports removal/insertion with active backplane bus (depending on CPU/rack version). Always check your system’s capability first. - Question: What happens if the output is short-circuited?
Answer: The voltage output is short-circuit protected (max. 25 mA current). The module will recover automatically after the fault is cleared. - Question: Which front connector do I need?
Answer: A 20-pin front connector (screw or spring type) is required – not included with the module. We stock compatible connectors separately.










Reviews