AI880A High Integrity Analog Input Module – Product Overview
The AI880A is a high-integrity 8-channel analog input module. It supports single or redundant configurations. Each channel accepts 0–20 mA or 4–20 mA signals. The module includes a supervised, current-limited transmitter supply per channel. It meets SIL3 (IEC 61508) and Category 4 (EN 954-1) standards. This module is ideal for safety-critical process control systems.
Key Features & Benefits
- 8 unipolar single-ended inputs – 0..20 mA or 4..20 mA, with HART pass-through
- Redundancy ready – supports single or redundant configurations for high availability
- Group isolated – all 8 channels isolated from ground in one group
- 12-bit resolution and fast 10 ms update cycle
- Advanced diagnostics – supervises internal voltage, field power input/output per channel
- NAMUR NE43 compliant with configurable over/under range limits
- Loop supervised DI function and configurable alarm limits
- Current limited transmitter power – protects field devices
- Certified for SIL3 (IEC 61508) and Category 4 (EN 954-1)
Technical Specifications
| Brand | ABB |
| Model | AI880A |
| Article Number | 3BSE039293R1 |
| Series | S800 I/O |
| Input Signal | 0..20 mA / 4..20 mA, unipolar single-ended |
| Channels | 8 |
| Resolution | 12 bit |
| Input Impedance | 250 Ω (with shunt stick TY801) |
| Accuracy | Max. 0.1% error |
| Temperature Drift | Max. 50 ppm/°C |
| Input Filter (rise time 0-90%) | 190 ms (HW filter) |
| Update Cycle | 10 ms |
| Over/Under Range | +12% (0..20 mA), +15% (4..20 mA) |
| NMRR (50/60 Hz) | > 40 dB |
| Max Field Cable Length | 600 meters (656 yards) |
| Max Non-Destructive Input | 11 V d.c. |
| Isolation | Groupwise isolated from ground |
| Rated Insulation Voltage | 50 V |
| Dielectric Test Voltage | 500 V a.c. |
| Power Dissipation | 2.4 W |
| Current Consumption (+5V Bus) | 45 mA |
| Current Consumption (+24V Bus) | max 50 mA |
| External Supply Current | 4 + transmitter current, max 260 mA |
Environmental & Certification
- Operating Temperature – 0 to +55 °C (+32 to +131 °F) ; approvals at +5 to +55 °C
- Storage Temperature – -40 to +70 °C (-40 to +158 °F)
- Relative Humidity – 5 to 95 % non-condensing
- Protection Class – IP20 (IEC 60529)
- Corrosion Protection – ISA-S71.04 G3
- Pollution Degree – 2 (IEC 60664-1)
- EMC – EN 61000-6-4 & EN 61000-6-2
- Electrical Safety – EN 61010-1, UL 61010-1, EN 61010-2-201
- Hazardous Locations – C1 Div 2 cULus, Zone 2 cULus, ATEX Zone 2
- Marine – ABS, BV, DNV, LR
- RoHS – DIRECTIVE 2011/65/EU
- WEEE – DIRECTIVE 2012/19/EU
Diagnostics & Status Indication
- Front LEDs: F(ault), R(un), W(arning)
- Supervision: internal voltage, field power input, field power output per channel
- Status: module error, module warning, channel error
- Advanced on-board diagnostics with configurable alarm limits
Compatibility & Mounting
- Compatible MTUs: TU834, TU844, TU845, TU854
- Keying code: FD
- Dimensions: 45 mm (W) x 102 mm (D) x 119 mm (H) ; 111 mm depth with connector
- Weight: 0.15 kg (0.33 lbs)
Installation & Maintenance
- Mount on standard S800 rail. Use TU834 MTU for single or redundant setups.
- Connect field devices to 2- or 3-wire transmitters with supplied power.
- Observe max cable length of 600 m for reliable signal.
- LED indicators simplify troubleshooting. No special tools required.
- Regularly check module status via supervision diagnostics.
Typical Applications
- Safety instrumented systems (SIS) up to SIL3
- Process control in oil & gas, chemical, and power plants
- High-integrity analog measurement for critical loops
- Redundant I/O configurations for high availability
- HART pass-through for smart transmitter communication
Frequently Asked Questions
Q: Is the AI880A compatible with HART?
Yes, it supports HART pass-through communication.
Q: Can I use it in a redundant system?
Yes, the AI880A is designed for both single and redundant configurations.
Q: What is the update cycle time?
The module updates every 10 ms.
Q: Does it have field power supervision?
Yes, it supervises field power input and output per channel.
Q: What certifications does it hold?
SIL3 (IEC 61508), Category 4 (EN 954-1), ATEX Zone 2, cULus, marine approvals.
Why Buy From Oiltech Controls?
- 15+ years in industrial automation spare parts
- Global shipment – FedEx, UPS, DHL available
- Tested surplus/refurbished options with full verification
- 12-month warranty on all products
- Technical verification before shipment
- Support for obsolete control systems
Ordering & Shipping
- Packaging: Anti-static, secure industrial packaging.
- Shipping: FedEx, UPS, DHL – worldwide express.
- Warranty: 12 months from date of invoice.
- Contact: info@oiltechcontrols.com or +86 158 8020 0923 (WhatsApp).
Copyright © 2026 Oiltech Controls Limited. All rights reserved.
Original Source: https://www.oiltechcontrols.com/










Reviews
There are no reviews yet.