1791DS-IB16 Safety Input Module – Key Facts
- Brand: Allen-Bradley / Rockwell Automation
- Model: 1791DS-IB16
- Series: Guard I/O 1791ES / 1791DS
- Inputs: 16 single-channel (safety)
- Nominal Voltage: 24V DC (19.2–28.8V range)
- Protection: IP20, short-circuit protected
- Temperature: -4°F to 140°F (-20°C to 60°C)
- Weight: 1.00 lbs (0.45 kg)
Technical Specifications (at a Glance)
- On-state voltage: 11V DC (min) | Off-state: 5V DC (max)
- On-state current: 3.3 mA (typ) | Off-state: 1.3 mA
- Output current (pulse test): 0.7 A per channel
- Output leakage: 0.1 mA (max) | Residual voltage: 1.2V (max)
- DeviceNet power: 11–25V DC
- Power consumption: 85 mA @ 24V DC
Built-in Safety & Diagnostics
- Electronic short-circuit protection on every input.
- Detects faults before they damage the module.
- Configurable pulse test outputs for sensor monitoring.
- Password-protected configuration lock for security.
- Supports single-channel and dual-channel safety devices.
Compatible Devices & Systems
- Emergency stop switches and light curtains.
- Safety interlock switches and door monitors.
- Two-hand controls and enabling devices.
- Works with GuardLogix and DeviceNet scanners.
- Ideal for OEM machinery and process safety loops.
Oiltech Controls’s Insight
- This module is a reliable choice for SIL 2 / PL d applications.
- Its 16 inputs allow efficient consolidation of safety signals.
- We recommend pairing it with a GuardLogix controller for best performance.
- For new installations, order the matching terminal base separately.
Professional FAQ – 5 Expert Answers
- Q: Can I use this module with non-safety sensors?
A: Yes, but we strongly advise using safety-rated sensors to maintain the system’s integrity. The module can monitor standard sensors, but the safety rating applies only when used with certified devices. - Q: How do I configure the pulse test outputs?
A: Use Rockwell’s RSNetWorx for DeviceNet. Set each output as pulse test source, 24V DC source, or standard output. Always test your configuration with a dummy load before going live. - Q: What is the maximum cable length for inputs?
A: Keep input wiring under 30 meters (98 feet) to avoid voltage drop and noise. For longer runs, use shielded cables and separate routing from power lines. - Q: Can I hot-swap this module?
A: No, the 1791DS-IB16 is not designed for hot-swapping. Always disconnect power before removal or insertion to prevent damage to the module or the backplane. - Q: Which controller is best for this module?
A: The GuardLogix series (e.g., 1756-L7x) offers native support. For older systems, use a DeviceNet scanner like the 1756-DNB. Check your controller’s firmware version for compatibility.
Order & Shipping Details
- Warranty: 12 months against manufacturing defects.
- Dispatch: 24–28 hours after order confirmation.
- Carriers: FedEx, UPS, DHL (tracked).
- Packaging: Anti-static bag with foam protection.
Why Buy From Oiltech Controls?
- 15+ years in industrial automation spare parts.
- Global shipping with real-time tracking.
- Tested surplus/refurbished options available.
- 12-month warranty on every order.
- Technical verification before shipment.
- Expert support for obsolete systems.
Contact us: info@oiltechcontrols.com | +86 158 8020 0923 (WhatsApp)