Product Brief: 1794-ADN DeviceNet Adapter
The Allen-Bradley 1794-ADN is a DeviceNet communication adapter for the FLEX I/O product family. It connects a FLEX I/O rack to a central DeviceNet scanner for data exchange. The module supports DIN rail or panel mounting. It has one DeviceNet port with data rates of 125, 250, or 500 Kbps. The adapter powers up to 8 FLEX I/O modules of any mix. Status LEDs indicate Mod/Net and I/O health. The 1794-ADN operates on 24 VDC (19.2-31.2 VDC range).
Technical Specifications
- Brand: Allen-Bradley (Rockwell Automation)
- Model: 1794-ADN
- Product Type: DeviceNet Adapter Module
- Communication Port: 1 x DeviceNet (open 5-pin or 10-pin plug)
- Data Rates: 125 Kbps, 250 Kbps, 500 Kbps
- Input Voltage: 24 VDC nominal (19.2 to 31.2 VDC)
- Current Draw: 400 mA @ 24 VDC
- DeviceNet Power: 90 mA @ 24 VDC
- FlexBus Output: 640 mA @ 5 VDC
- Power Dissipation: 7.6 W max at 19.2 VDC
- Isolation Voltage: 50 V continuous (tested at 1930 VDC)
- Indicators: Mod/Net Status (red/grn), I/O Status (red/grn)
- Address Setting: Thumbwheel switches (00-63)
- Operating Temp: 0 to 55 °C (32 to 131 °F)
- Storage Temp: -40 to 85 °C (-40 to 185 °F)
- Vibration: 5 g @ 10-500 Hz
- Shock (operating): 30 g @ 11 ms
- Dimensions: 3.7 x 3.6 x 3.4 in
- UPC: 10612598140166
Installation & Configuration
- Mount on DIN rail or panel; place as the leftmost module in the rack.
- Set node address via thumbwheel switches (range 00-63).
- Baud rate is auto-detected during power-up.
- Use Belden YR-29832 or equivalent DeviceNet cable.
- Maximum wire size: 12 AWG stranded with 3/64 in insulation.
- Provide a 24 VDC supply capable of 14A inrush for 5 ms.
- Supports up to 8 FLEX I/O modules in any combination.
Professional FAQ (Experience-Based)
- Q: Can I use this adapter with third-party DeviceNet masters?
Yes, as long as the master supports standard DeviceNet protocol. We have tested it with several non-Rockwell scanners. - Q: What is the maximum cable length for this adapter?
For 125 Kbps, up to 500 m; for 250 Kbps, up to 250 m; for 500 Kbps, up to 100 m. Use proper termination resistors. - Q: How do I troubleshoot if the module doesn’t go online?
Check the thumbwheel address (ensure unique on the network), baud rate match, and cable termination. Status LEDs give specific error codes. - Q: Can I hot-swap I/O modules behind the 1794-ADN?
Yes, FLEX I/O modules are hot-swappable, but the adapter itself must be powered down for removal. - Q: What power supply rating do I need?
Provide 24 VDC, 400 mA minimum, but consider inrush of 14A for 5 ms. We recommend a supply with at least 2A capacity for multiple modules.