CC-PAIL51 Honeywell Low Level Analog Output – TC and RTD Input Module
The CC-PAIL51 is a low level analog output module from Honeywell. It accepts thermocouple or RTD signals on every channel. Each channel is fully isolated from the others and from the power system. The module scans all inputs once per second. It uses a fixed 50 Hz or 60 Hz line frequency integration. Cold junction compensation covers -20 to +60 °C. The CC-PAIL51 pairs with the CC-TAIL51 16-point IOTA. This module suits temperature monitoring in process plants. It delivers stable readings with low drift and strong noise rejection.
Input and Channel Specifications
- Input type: Thermocouple or RTD, configurable per channel
- Input channels: Fully isolated, channel to channel and channel to power system
- Input scan rate: 1 second
- Channel bandwidth: 0 to 4.7 Hz at -3 dB
- Nominal TC range: -20 to +100 millivolts
- Max normal mode input (TC): -10 to +10 volts, non-damaging
- Max normal mode input (RTD): -1 to +2 volts at 100 milliamps
- Input impedance: 1 megohm at DC, TC only
- RTD excitation current: 1 milliamp
- RTD max lead resistance: 15 ohms
Accuracy and Stability
- Gain error: 0.050 % full scale max
- TC and millivolt stability: ±20 ppm per max
- RTD stability: ±20 ppm per max
- Long term drift: 500 ppm
- TC linearization accuracy: ±0.05 ohms per °C
- Cold junction compensation: -20 to +60 °C, ±0.5 °C typical
Isolation and Noise Rejection
- CMV vs power system common: ±250 VDC or VAC RMS, DC to 60 Hz
- CMRR at 50 or 60 Hz: 120 dB min with 1000 ohm source
- Channel-to-channel voltage: ±250 VDC or VAC RMS, DC to 60 Hz
- Crosstalk: 80 dB DC to 60 Hz, 120 dB at 50 and 60 Hz
- NMRR at 50 or 60 Hz: 60 dB min
- Line frequency integration: Fixed 50 Hz or 60 Hz selection
Supported Sensor Types
- Thermocouple J: -200 to +1200 °C
- Thermocouple K: -100 to +1370 °C
- Thermocouple E: -200 to +1000 °C
- Thermocouple T: -230 to +400 °C
- Thermocouple B: +100 to +1820 °C
- Thermocouple S: 0 to +1700 °C
- Thermocouple R: 0 to +1700 °C
- Millivolt input: -20 to +100 millivolts
- RTD Pt 100 DIN 4376: -180 to +800 °C
- RTD Pt 100 JIS C-1604: -180 to +650 °C
- RTD Ni 120 ED #7: -45 to +315 °C
- RTD Cu 10 SEER: -20 to +250 °C
- RTD Cu 50 SEER: -50 to +150 °C
Open Thermocouple Detection
- Each conversion is qualified for open sensor detection.
- ≤ 1000 ohms guarantees no trip.
- 1500 ohms guarantees trip.
- This prevents false alarms during normal operation.
Environmental and Physical Data
- Operating temperature: -40 to +70 °C
- Storage temperature: -40 to +85 °C
- IOTA: CC-TAIL51, 16 point, 9 inch