CC-PDIL01 Honeywell 24VDC Digital Input Module – 32-Channel Series C I/O
CC-PDIL01 is a Honeywell Series C 24VDC Digital Input module with 32 channels. It reads 24VDC discrete signals from field devices. The module offers extensive internal diagnostics, open-wire detection, and optional redundancy. It suits continuous process control and safety-related monitoring. Galvanic isolation protects the IOM from field transients. On-board excitation power removes the need for marshalling power. The module also supplies non-incendive field power. Users can select internal or external field power. Direct or reverse input indication helps commissioning.
Why Buy From Oiltech Controls?
- 15+ years in industrial automation spare parts
- Global shipment support via FedEx, UPS, and DHL
- Tested industrial surplus and refurbished options
- 12-month warranty on every module
- Technical verification before shipment
- Support for obsolete control systems
Technical Specifications
| Brand | Honeywell |
| Model | CC-PDIL01 |
| Series | Series C I/O |
| Module Type | 24VDC Digital Input |
| Input Channels | 32 |
| DI Power Voltage Range | 18 to 30 VDC |
| ON Sense Voltage / Current | 13 VDC min or 3 mA min |
| OFF Sense Voltage / Current | 5 VDC max or 1.2 mA max |
| Input Impedance | 4.2 kΩ |
| Absolute Delay | 5 ms ±20% across input filter and isolation |
| Galvanic Isolation | 1500 VAC RMS or ±1500 VDC |
| Isolation Technique | Optical, in IOM |
| Field Resistance for ON | 300Ω max @ 15VDC |
| Field Resistance for OFF | 30 kΩ min @ 30VDC |
| Measurement Range | 24VDC discrete input, 18–30VDC field power |
| Frequency Response | Filtered input, 5 ms response delay |
| Sensitivity | 3 mA ON, 1.2 mA OFF threshold |
| Linearity | Digital threshold detection, no analog linearity |
| Resolution | 1-bit per channel, 32 discrete states |
| Temperature Range | Industrial control cabinet range, refer to Honeywell Series C IOM manual |
| Environmental Tolerance | Designed for process cabinet environments |
| Anti-interference | Galvanic isolation and input filtering |
IOTA Compatibility
- CC-TDIL01 – Non-redundant, 9 inch
- CC-TDIL11 – Redundant, 12 inch
- CC-GDIL11 – Redundant, 12 inch
- CC-GDIL21 – Non-redundant, 6 inch
- CC-GDIL01 – Redundant for explosion protection, 12 inch
- CC-SDXX01 – GI-IS I/O Expander, 12 inch
Diagnostics Capability
The module performs extensive internal diagnostics for data integrity. It detects and annunciates open field wire conditions. A channel with open-wire diagnosis reports its PV as invalid. This blocks incorrect control action. Optional redundancy adds another layer of availability.
Installation Guide
Mount the IOTA on the Series C rail. Seat the CC-PDIL01 IOM firmly. Select internal or external field power before wiring. Use shielded twisted pairs for field inputs. Keep input wiring away from high-voltage cables. Verify ON and OFF thresholds after wiring. Check open-wire flags during loop checkout.
Commissioning and Maintenance
Use direct or reverse input indication to match field logic. The on-board excitation power simplifies loop checkout. No marshalling power is needed. Read channel diagnostics from the control system. Replace a faulty module only after technical verification. Redundant IOTA options allow online service in many cases.
Typical Applications
- Discrete valve position feedback
- Pump and motor run status
- Limit switch and proximity sensor inputs
- Alarm and trip contact monitoring
- Safety-related discrete monitoring with open-wire detection
Certifications and Compliance
The module supports non-incendive field power supply. Galvanic isolation meets 1500 VAC RMS or ±1500 VDC. Refer to the Honeywell Series C documentation for the full certification list for your IOTA and cabinet configuration.
Packing List and Warranty
- 1 x CC-PDIL01 Digital Input Module
- 1 x Anti-static protective bag
- 1 x Test verification record
- 12-month warranty included
- Shipping by FedEx, UPS, or DHL
FAQ
Q: How many channels does CC-PDIL01 have?
A: It has 32 digital input channels.
Q: Does it detect broken field wiring?
A: Yes. It flags open-wire conditions and marks the PV invalid.
Q: Can I use redundant IOTA bases?
A: Yes. Redundant IOTA options include CC-TDIL11, CC-GDIL11, and CC-GDIL01.
Q: What is the input voltage range?
A: The DI power range is 18 to 30 VDC.
Q: Is a warranty included?
A: Yes. Every module carries a 12-month warranty.
Contact Oiltech Controls
Email: info@oiltechcontrols.com
Phone / WhatsApp: +86 158 8020 0923
Copyright © 2026 Oiltech Controls Limited. All rights reserved.
Original Source: https://www.oiltechcontrols.com/
All rights reserved.










Reviews