1606-XLE960MX-3N Allen-Bradley Power Supply – 3-Phase 48 V DC, 960 W, Bulletin 1606-XL
The 1606-XLE960MX-3N is an Essential-class switched-mode supply in the Allen-Bradley Bulletin 1606-XL line. It runs on 3-phase AC 400/480 V and delivers a semi-regulated 48 V DC output at 960 W and 20 A. Efficiency hits 96.0% typical, with losses near 40 W. The design uses screw terminals and a DIN rail body. Ripple runs up to 2500 mVpp because the output is semi-regulated. Power factor is 0.93 typical. This unit is End of Life. Rockwell discontinues it December 31, 2026. The engineering replacement is 1606-XLS960F. Buyers still running 3-phase 48 V panels should plan a migration path now.
Specification Snapshot
Brand: Allen-Bradley | Model: 1606-XLE960MX-3N | Series: Bulletin 1606-XL | Class: Essential
- Input: 3-phase AC 400 V / 480 V
- Output: DC 48 V, semi-regulated
- Current: 20 A nominal
- Rated power: 960 W
- Efficiency: 96.0% typical; losses 40.0 W typical
- Ripple and noise: 2500 mVpp maximum
- Power factor: 0.93 typical
- Derating: 24 W/°C from +60…+70 °C
- Operating temperature: -25…+70 °C
- Storage temperature: not published in 1606-TD002
- Humidity: not published in 1606-TD002
- Protection rating: IP20
- Terminals: screw
- Dimensions (H×W×D): 124 × 96 × 159 mm
- Weight: 1.40 kg
- Communication: none; no ports, no protocol
- Approvals: UL 60950-1, cUL, CE per Bulletin 1606 standard
Lifecycle Alert
- Status: End of Life, announced by Rockwell
- Discontinued: December 31, 2026
- Engineering replacement: 1606-XLS960F
- Plan spare stock before the cutoff date
- Verify panel wiring before a swap to the replacement
What This Supply Suits
- 3-phase cabinets feeding 48 V DC motor brakes and contactors
- Heavy 48 V loads where tight regulation is not critical
- Legacy panels built around the 1606-XLE footprint
- High-power DC bus segments near 1 kW
- Retrofit jobs that must match existing screw-terminal wiring
Wiring and Start-Up
- Mount on DIN rail. Keep airflow paths open.
- Feed all three phases at 400 V or 480 V AC.
- Use screw terminals. Torque to spec.
- Accept the semi-regulated 48 V. Expect ripple up to 2500 mVpp.
- Apply derating above +60 °C: 24 W/°C.
- Check phase rotation and balance at commissioning.
Oiltech Controls Review
This is a workhorse unit, not a precision rail. The 96% efficiency keeps heat down at 960 W. The semi-regulated output is fine for contactors and brakes. It is not fine for sensitive 48 V electronics. Ripple at 2500 mVpp is high by design. The EOL date matters most. If your panel depends on this footprint, buy tested spares now.
Oiltech Controls Insight
- Reserve stock before December 31, 2026.
- Ask for ripple and load-bank test data on used units.
- Match the replacement 1606-XLS960F to your load type first.
- Do not pair with sensitive 48 V logic without filtering.
Why Buy From Oiltech Controls?
- 15+ years in industrial automation spare parts
- Worldwide shipping with tracking
- Tested surplus and refurbished units
- 12-month warranty on every supply
- Technical verification before dispatch
- Obsolete system support after OEM cutoff
- Dispatch in 24-28 hours
- Couriers: FedEx, UPS, DHL
Warranty Terms
- 12 months from invoice date
- Covers material and workmanship defects
- Excludes overvoltage, misuse and moisture damage
- Claim with order number and fault description
FAQ
Can I replace 1606-XLE960MX-3N with 1606-XLS960F directly?
Check wiring, footprint and load type first. The replacement is regulated and may need different fusing. Ask us for a comparison sheet before you swap.
Why is ripple so high at 2500 mVpp?
The output is semi-regulated by design. Use filtering if your load is sensitive. Contactors, brakes and lamps tolerate it well.
Should I stock spares before the EOL date?
Yes. Rockwell discontinues the unit on December 31, 2026. Tested spares protect uptime after that cutoff.
What should I verify on a used unit?
Ask for load-bank data, ripple measurement and screw-terminal condition. Oiltech Controls tests each unit before shipment.
Is this unit right for a new panel design?
No. Choose the current regulated 1606-XLS960F for new builds. Keep the 1606-XLE960MX-3N for legacy maintenance only.
Contact Information
Email: info@oiltechcontrols.com
WhatsApp: +86 158 8020 0923
Copyright © 2026 Oiltech Controls Limited. https://www.oiltechcontrols.com/ All rights reserved.
All rights reserved.










Reviews