1762-IR4 Four Channel RTD and Resistance Input Module
1762-IR4 is an Allen-Bradley MicroLogix expansion module. It carries four RTD and resistance input channels. A Sigma-Delta converter turns sensor resistance into digital data. The module fits MicroLogix 1100, 1200, and 1400 controllers. It supports 2-wire, 3-wire, and 4-wire RTD wiring. Heat dissipation is 1.5 W. Size is 90 x 87 x 40 mm. It mounts on DIN rail or a panel. One diagnostic LED shows status and power. The module auto-calibrates on channel enable. Users can also set calibration every 5 minutes. This part suits temperature loops that need stable RTD readings in compact MicroLogix racks.
Key Technical Data
- Brand: Allen-Bradley
- Model: 1762-IR4
- Manufacturer: Rockwell Automation
- Family: MicroLogix
- Inputs: Four, RTD or resistance
- Converter: Sigma-Delta
- RTD types: Pt 385 and Pt 3916 at 100, 200, 500, 1000 ohm; Cu 426 at 10 ohm; Ni 672 and Ni 618 at 120 ohm; Ni-Fe 518 at 604 ohm
- Wiring: 2-wire, 3-wire, 4-wire RTD; 2-wire, 3-wire resistance
- Resistance ranges: 0 to 150, 0 to 500, 0 to 1000, 0 to 3000 ohm
- Filters: 10 Hz, 50 Hz, 60 Hz, 250 Hz, 500 Hz, 1 kHz
- Data formats: Raw, engineering units x1, x10, scaled for PID, percent full scale
- Bus power: 5V and 24V DC via 1762 bus
- Heat dissipation: 1.5 W
- Dimensions: 90 x 87 x 40 mm
Ordering and Delivery
- 12-month warranty on eligible units.
- 24 to 28 hour dispatch on stocked items.
- Shipping by FedEx, UPS, or DHL.
- Email info@oiltechcontrols.com or WhatsApp +86 158 8020 0923.
Frequently Asked Questions
Q: Will 1762-IR4 work in my MicroLogix 1400 rack?
A: Yes. It fits MicroLogix 1100, 1200, and 1400 controllers. Check the rack power budget and the number of allowed expansion modules first.
Q: Why does my RTD reading jump or drift?
A: Most drift comes from lead resistance or electrical noise. Switch to 3-wire or 4-wire RTD wiring. Route sensor cables away from drives and relays.
Q: Should I use the 10 Hz or 1 kHz filter?
A: Use 10 Hz for steady temperature and best noise rejection. Use 1 kHz only when fast update matters. High filter rates shorten update time but let more noise through.
Q: How do I choose between an RTD input and a resistance input?
A: Pick RTD mode when you read temperature directly. Pick resistance mode for position or displacement sensors. Confirm your sensor range sits inside 0 to 3000 ohm.
Q: What should I verify before buying a used 1762-IR4?
A: Ask for a test report with live RTD readings on all four channels. Confirm the diagnostic LED works. Check the label and firmware. A 12-month warranty adds real protection.