3500/20-01-02-00 | Bently Nevada Rack Interface Module
The 3500/20-01-02-00 is the primary communication gateway for the Bently Nevada™ 3500 monitoring system. This Rack Interface Module (RIM) resides in slot 1 and enables configuration, data acquisition, and host software integration. It does not affect critical monitoring paths, ensuring high system availability.
Product Overview
- Type: Standard RIM (01) with RS232/RS422 I/O (02).
- Agency Approval: None (00).
- Position: Slot 1, next to power supplies.
- Compatibility: TDXnet, TDIX, DDIX, and 3500 Host Software.
- TMR Support: Optional TMR version for channel comparison.
- Protocol: Bently Nevada proprietary (auto-baud capable).
Key Technical Specifications
| Brand | Bently Nevada |
| Model | 3500/20-01-02-00 |
| Series | 3500 Series |
| Rack Interface Type | Standard RIM (01) |
| I/O Module Type | RS232/RS422 (02) |
| Power Consumption | 4.75 W (typical) |
| Front Panel Comms | RS232, 38.4 kbaud |
| I/O Module Comms | RS232/RS422, 38.4 kbaud |
| Modem I/O | 14.4 kbaud (Hayes AT-compatible) |
| Data Manager I/O | 9600 baud (fixed) |
| Rack Connector | RS422, 38.4 kbaud |
| Operating Temperature | -30°C to +65°C |
| Storage Temperature | -40°C to +85°C |
| Humidity | 95% (non-condensing) |
| Dimensions (RIM) | 241.3 x 24.4 x 241.8 mm |
| Weight (RIM) | 0.91 kg |
| I/O Module Dimensions | 241.3 x 24.4 x 99.1 mm |
| I/O Module Weight | 0.45 kg |
Environmental & Mechanical
- Wide temperature range: -30°C to +65°C for reliable operation.
- Storage: -40°C to +85°C.
- Humidity tolerance: 95% non-condensing.
- Rack slots: 1 full-height front slot (RIM) + 1 rear slot (I/O).
Diagnostics & Indicators
- OK LED – confirms proper RIM operation.
- TX/RX LED – active communication with rack modules.
- TM LED – indicates Trip Multiply mode.
- CONFIG OK LED – valid rack configuration.
- I/O Module OK Relay – normally energized; selectable OPEN/CLOSED for fault annunciation.
- Rack Reset Button – clears latched alarms and Timed OK Channel Defeat.
Installation & Commissioning
- Slot 1 mounting – mandatory location next to power supplies.
- Address switch – set 1 of 63 possible rack addresses.
- RS232/RS422 switch – select interface type for host software.
- Cable lengths: RS232 up to 30 m; RS422 up to 1200 m.
- Modem cable: 2.1 m max (to phone jack).
- Data Manager I/O: 3 m cable max.
Compatibility & Integration
- Supports TDXnet, TDIX, and DDIX processors.
- Works with Bently Nevada Host Software for configuration and data collection.
- For TMR systems, use the TMR RIM version for channel voting and comparison.
- Modem I/O supports Hayes AT commands (14.4 kbaud).
- Data Manager I/O provides static/dynamic data to TDIs and DDIX.
Certifications & Warranty
- Agency Approval: None (00).
- Warranty: 12 months from shipment.
- Quality: Tested for industrial surplus/refurbished reliability.
- Shipping: FedEx, UPS, DHL (global).
Typical Applications
- Machinery condition monitoring in oil & gas, power generation, and heavy industry.
- Interface to SCADA and DCS systems via RS232/RS422.
- Data aggregation for predictive maintenance and diagnostics.
Diagnostic Capabilities
- Channel comparison (TMR) – detects deviations > configured threshold.
- System event logging – flags monitor errors and rack faults.
- OK relay indicates normal or fault condition for external monitoring.
Frequently Asked Questions
- What is the default protocol? Bently Nevada proprietary (auto-baud).
- Can I use a standard modem? Yes, with Hayes AT-compatible modem I/O.
- Is the RIM required for each rack? Yes, one per rack.
- How do I reset alarms? Use the front panel reset button or I/O module contact.
- What is the maximum cable length for RS422? 1200 metres.
- Does the RIM affect monitoring path? No, it is not in the critical path.
Why Buy From Oiltech Controls?
- 15+ years of expertise in industrial automation spare parts.
- Global shipment via FedEx, UPS, DHL.
- Tested industrial surplus and refurbished options with full functionality.
- 12-month warranty on every product.
- Technical verification before shipment to ensure performance.
- Support for obsolete control systems and legacy parts.
Contact us: info@oiltechcontrols.com | +86 158 8020 0923 (WhatsApp)
Explore our Modicon Quantum series and other automation solutions.
Copyright © 2026 Oiltech Controls Limited. All rights reserved.
Original Source: https://www.oiltechcontrols.com/










Reviews