6AG1307-1KA02-7AA0 SIPLUS S7-300 PS 307 10 A Power Supply
The 6AG1307-1KA02-7AA0 is a SIPLUS variant of the S7-300 PS 307 supply. It is based on 6ES7307-1KA02-0AA0 and adds conformal coating. Input takes 120 or 230 V AC and output holds a stable 24 V DC at 10 A. The coated board runs from -25 to +70 °C. SELV output meets EN 60950-1 and EN 50178. Efficiency sits near 90% at rated load. This unit suits plants with humidity, dust, and chemical exposure.
Input Side
- 120 V AC: 85 to 132 V AC, 4.2 A rated
- 230 V AC: 170 to 264 V AC, 1.9 A rated
- Line frequency: 47 to 63 Hz
- Overvoltage strength: 2.3x Ue rated for 1.3 ms
- Inrush current: 55 A max at 25 °C, 3 ms
- Mains buffering: 20 ms min at rated load
- Leakage current: 0.6 mA typical, 3.5 mA max
Output Side
- Rated output: 24 V DC, 10 A
- Range: 23.27 to 24.72 V DC
- Derating: 7 A above 60 °C
- Ripple: 15 mV typical, 50 mV max peak-peak
- Overvoltage cutoff: below 28.8 V, auto restart
- Short-circuit trip: electronic, auto restart
- Continuous short-circuit current: 12 A max
- Power loss: 27 W typical at rated load
Environment and Standards
- Operating temperature: -25 to +70 °C, 60 °C for UL/cUL, ATEX, FM
- Humidity: up to 100% with condensation, IEC 60068-2-38
- Altitude: up to 2000 m at full load
- Immunity: EN 61000-6-2
- Emission: EN 55022 Class B
- Protection class: I with protective conductor
- Approvals: CE, UL 94-HB housing
- Size and weight: 80 × 125 × 120 mm, 0.8 kg
Suitable Equipment
- S7-300 PLC racks in coated panels
- Outdoor or washdown cabinets with humidity swings
- Chemical and process plants with Class 3C4 gas
- Ship and offshore rooms with salt spray
- Retrofit cells replacing 6ES7307-1KA02-0AA0 units
FAQ
Q: Can I drop this unit into a rack wired for 6ES7307-1KA02-0AA0?
A: Yes. The SIPLUS version shares the base design. Check the 24 V rail load and wiring before swap.
Q: How much current can I pull at 65 °C cabinet temperature?
A: Plan for 7 A, not 10 A. Derating starts above 60 °C.
Q: What does conformal coating change in practice?
A: It resists humidity, dust, and chemical gas. It does not add waterproofing to connector pins.
Q: Is 100% humidity with condensation really allowed?
A: The unit is tested for it. However, do not commission under condensation. Dry the panel first.
Q: What should I check on a used SIPLUS PS 307?
A: Ask for 24 V output readings under load, coating photos, and fan-free heatsink checks. Confirm the 12-month warranty.