CC-PAIH51 Honeywell Experion Series-C I/O
The CC-PAIH51 is a high-level analog input module with HART from Honeywell’s Experion Series-C I/O family. It handles 16 single-ended current channels for 2-wire or self-powered transmitters. The module reads 4-20 mA through a 200 Ω resistor. A 16-bit A/D converter delivers precise process data. Field power conditioning includes individually protected current limiting circuits for Class 1, Div 2 non-incendive interfacing. No fusing required.
Technical Data
- Model: CC-PAIH51
- Brand: Honeywell
- Series: Experion Series-C I/O
- Type: High-Level Analog Input with HART
- Input channels: 16, all single ended
- Input range: 4-20 mA only (through 200 Ω)
- A/D resolution: 16 bits
- Input scan rate: 50 ms
- CMRR: 70 dB (dc to 60 Hz, 500 Ω imbalance)
- Common mode voltage: -6 to +5 V peak
- NMRR at 60 Hz: 19 dB
- Normal mode filter: single-pole RC, -3 dB @ 6.5 Hz
- Max normal mode input: ±30 V
- Crosstalk: -60 dB (dc to 60 Hz)
- Accuracy at 23.5°C: ±0.075% of full scale
- Accuracy at 0-60°C: ±0.15% of full scale
- Field power: individually protected current limiting
- IOTA options: CC-TAIX51 (non-redundant, 6″), CC-TAIX61 (redundant, 12″)
FAQ
Q: Can the CC-PAIH51 read HART digital signals from my transmitter?
A: Yes. The module supports HART communication. It passes digital data to the Experion controller. You can configure transmitters remotely. Confirm your system firmware supports HART pass-through.
Q: What is the difference between CC-TAIX51 and CC-TAIX61 IOTA boards?
A: CC-TAIX51 is non-redundant and 6 inches wide. CC-TAIX61 is redundant and 12 inches wide. Both accept the CC-PAIH51 module. Choose based on your availability and redundancy needs.
Q: How often should I calibrate the CC-PAIH51?
A: Honeywell recommends annual calibration. The module holds ±0.075% accuracy at 23.5°C. Drift is low. For critical loops, calibrate every six months. Always use a certified current source.
Q: Can I use self-powered transmitters with this module?
A: Yes. The CC-PAIH51 accepts 2-wire and self-powered transmitters. Field power conditioning protects each channel. No external fuses are needed for Class 1, Div 2 areas.
Q: What should I check when buying a used CC-PAIH51?
A: Ask for channel-by-channel test data. Check the IOTA connector pins for corrosion. Verify HART communication works. Oiltech Controls tests each unit and provides a 12-month warranty.