FCAN-01 | ABB CANopen Adapter Module
The FCAN-01 adds CANopen connectivity to ABB drives. It slides into the drive option slot and links the drive to any CANopen-compliant device. The bus side is functionally isolated. The PCB is conformal coated. Baud rates run from 50 kBit/s to 1 Mbit/s. Bus length scales with speed, up to 1000 m at 50 kBit/s. The module suits networked drive panels and multi-axis lines.
Ports and Indicators
- X2: 20-pin connector to the drive.
- X1: 9-pin male D-SUB bus connector.
- LEDs: three bicolor indicators (HOST, MODULE, NETWORK).
- Power: +3.3 V ±5%, max. 300 mA from the drive.
- Mounting: drive option slot.
- Protection: IP20.
CANopen Link Data
- Protocol: CANopen.
- Serial type: asynchronous, half-duplex, CAN.
- Max transfer rate: 1 Mbit/s.
- Rate options: 1 Mbit/s, 500, 250, 125, 100, 50 kBit/s.
- Medium: shielded twisted pair, 120 Ω nominal impedance.
- Termination: 120 Ω or active circuitry at each trunk end.
- Termination note: not built into the adapter module.
Bus Length by Baud Rate
- 1 Mbit/s: 25 m.
- 500 kBit/s: 100 m.
- 250 kBit/s: 250 m.
- 125 kBit/s: 500 m.
- 50 kBit/s: 1000 m.
Compliance and Environment
- EMC: complies with EN 61800-3:2004.
- Bus isolation: functionally isolated from the drive.
- Coating: conformal coated PCB.
- Ambient: follows the host drive manual limits.
Compatible Equipment
- ABB drives with a free option slot
- CANopen networks with standard masters
- Multi-axis lines needing bus control
- Panels requiring isolated bus interfaces
- Legacy ABB drive upgrades
FAQ
Does the FCAN-01 include bus termination?
No. Add 120 Ω or active termination at both trunk ends. Unterminated trunks cause bus errors.
Which baud rate should I start with?
Start at 250 or 500 kBit/s for most panels. Lower the rate only when cable runs demand it.
Why does the NETWORK LED stay red?
Check termination, node ID and baud rate. Verify CAN_H and CAN_L wiring. Confirm the master is online.
Can I use standard twisted pair cable?
Prefer CANopen-approved 120 Ω cable. Shielded twisted pair works if impedance matches. Bond the shield at one end.
What should I record before replacing the module?
Save node ID, baud rate and PDO mapping. Note the master configuration. Reload settings after fitting the new card.










Reviews