FRSA-00 | ABB RS-485 Adapter Board for ACS350 Modbus-RTU
The FRSA-00 is an RS-485 adapter board from ABB. It adds a two-wire Modbus-RTU link to the ACS350 drive family. The board carries a built-in 120 ohm termination resistor. It works alongside the FMBA-01 Modbus RTU adapter module. The link is asynchronous, half-duplex RS-485. Top speed is 115.2 kb/s. Use shielded twisted pair cable with 100 to 150 ohm impedance. The board fits trunk-line networks with short drop lines. Engineers pick it for legacy ACS350 panels that need a simple serial fieldbus connection.
Serial Link Characteristics
- Physical layer: two-wire RS-485 with signal ground.
- Mode: asynchronous, half-duplex, multipoint.
- Protocol: Modbus-RTU.
- Topology: trunk line; drop lines allowed.
- Cable: shielded twisted pair, 100 to 150 ohms.
- Termination: 120 ohms, built into the FRSA board.
- Max transfer rate: 115.2 kb/s.
- Bus bias: applied voltage between -7 V and +12 V DC.
Grounding and Bus Integrity
- Tie the RS-485 signal ground of every node to one common potential.
- Long runs can build large ground voltage differences.
- Ground offset plus data swing must stay inside the bus window.
- Excess offset can drop data or damage the port.
- Follow TSB89, Application Guidelines for TIA-EIA-485-A.
Technical Data
- Model: FRSA-00
- Brand: ABB
- Type: RS-485 adapter board
- Protocol support: Modbus-RTU
- Partner module: FMBA-01 Modbus RTU adapter
- Drive family: ACS350
- Max speed: 115.2 kb/s
- Termination: 120 ohms, on board
Shipping, Warranty and Stock
- We dispatch in 24-28 hours.
- Shipment runs through FedEx, UPS and DHL.
- Every board carries a 12-month warranty.
- We verify each unit before it leaves.
- Ask us for current stock and lead time.
FAQ
Q: Does the FRSA-00 include the 120 ohm resistor?
A: Yes. The termination is built into the board. You still need a resistor at the far end of the trunk if that node has none.
Q: Can I mix FRSA-00 and FMBA-01 on one network?
A: Yes. Both support two-wire RS-485 Modbus-RTU. Set the same baud rate and parity on every node.
Q: My bus drops data on long cable runs. What should I check?
A: Measure the ground potential difference between nodes first. Add a signal ground wire and check termination. Keep the pair away from VFD output cables.
Q: Which cable should I buy for an ACS350 network?
A: Use shielded twisted pair with 100 to 150 ohm impedance. Belden 3105A or similar works well. Ground the shield at one end.
Q: Is FRSA-00 still the right choice for a new build?
A: For ACS350 panels already on Modbus, yes. For new designs, send us the drive model and we will confirm the best serial or fieldbus option.