MTL5018AC Dual-Channel Relay Interface – Hazardous Area Control Solution
Safe Control for Dangerous Locations
The MTL5018AC converts signals from explosive areas into safe relay outputs. Controls two devices with phase reversal and automatic fault detection for maximum safety.
Key Benefits
- Two relay outputs (250V/2A)
- Works with NAMUR sensors
- Automatic fault detection
- Independent phase control
- Clear LED status indicators
Technical Specifications
| Model: | MTL5018AC (Full: MTL5018AC-RK-10-0-0) |
| Input Type: | NAMUR/DIN 19234 |
| Relay Contacts: | 250V AC/2A, 40V DC/2A |
| Response Time: | <10ms |
| Power Supply: | 85-265V AC, 45-65Hz |
| Temp Range: | -20°C to +60°C |
| Fault Detection: | Open/short circuit |
Simple Wiring
- 1-2: Channel 1 sensor
- 4-5: Channel 2 sensor
- 10-12: Channel 1 relay
- 7-9: Channel 2 relay
- 13-14: AC power
Safety Certified
Approved for Zone 0 IIC T4-T6 and Division 1 Group A hazardous locations. Meets explosion protection standards.
Package Contents
- 1 MTL5018AC unit
- Installation guide
- Terminal labels
Expert Questions
- What sensors work with it?
All NAMUR-type proximity detectors. - Can I disable fault detection?
Yes – via top panel switches. - What do LED colors mean?
Green=power, Yellow=active, Red=fault - Maximum cable length?
100m with proper shielding. - Need external power for sensors?
No – provides 7-9V sensor power.
Shipping & Warranty
Fast global shipping via FedEx/UPS/DHL. Your MTL5018AC includes 12-month performance guarantee.