Product Brief – 6ES7331-7PF11-0AB0
6ES7331-7PF11-0AB0 is a dedicated thermocouple input module for SIMATIC S7-300 systems. It provides 8 isolated analog channels for TC types B, C, E, J, K, L, N, R, S, T, U, and TXK/TXK(L) per GOST. The 16‑bit resolution and 50 ms conversion time deliver reliable temperature readings. Use it in high‑channel‑count temperature monitoring applications.
Core Technical Data
- Brand: Siemens
- Model: 6ES7331-7PF11-0AB0
- Series: SIMATIC S7-300
- Module Type: SM 331 – 8 AI, isolated thermocouple
- Channels: 8 (thermocouple only – no voltage/current)
- Resolution: 16 bit (two’s complement)
- Conversion time: up to 4 ch: 10 ms/module; ≥5 ch: 190 ms/module
- Power loss: typ. 3 W
- Backplane current: max. 100 mA (5 V DC)
- Load voltage L+: 24 V DC (reverse polarity protected)
Thermocouple Support & Accuracy
- Supported TC types: B, C, E, J, K, L, N, R, S, T, U, TXK/TXK(L) (GOST)
- Linearization: parameterizable for all supported types
- Basic error (25 °C): as low as ±0.02 % (type C) to ±0.67 % (TXK lower range)
- Operational error (full temp): approx. ±0.08..1.00 % depending on TC type
- Temperature compensation: internal, external Pt100, or compensation socket
Diagnostics & Alarms
- Parameterizable diagnostic alarm (per group)
- Limit value alarm for process supervision
- Hardware interrupt per channel (0‑7)
- Readable diagnostic information via STEP 7
- Group error SF (red) LED for quick fault indication
Isolation & Physical Details
- Galvanic isolation between channels (groups of 2) and backplane bus
- Test voltage: 500 V DC
- Shielded cable length: max. 100 m
- Dimensions (WxHxD): 40 x 125 x 120 mm, weight ~272 g
- Requires 40‑pin front connector (not included)
Compatibility & Suitable Equipment
- Works with S7‑300 CPUs (e.g., 314, 315, 317) and ET 200M remote stations
- Engineering via STEP 7 V5.x or TIA Portal (GSD integration)
- Ideal for temperature monitoring in kilns, furnaces, and chemical reactors
- Supports thermocouple types common in Eastern European (GOST) applications
- Not for RTD, resistance, or voltage/current signals










Reviews