1791-8BC – 16-Point Combination Discrete I/O Module
Brand: Allen‑Bradley | Series: 1791 Block I/O | Type: Discrete Input / Output Module
This 16‑channel block I/O module delivers 8 DC inputs and 8 DC outputs in a compact, rackless design. It supports RIO communication and is suited for distributed control architectures. Vertical or horizontal mounting options allow flexible panel placement.
Oiltech Controls’s Insight
- Proven for legacy PLC‑2, PLC‑5, SLC 500, and Logix platforms via RIO.
- Output current derates with temperature – vertical mounting gives 500 mA @ 60 °C.
- Supports 57.6K, 115.2K, and 230.4K baud; use correct termination resistors.
- Ideal for distributed I/O where space is limited and wiring is centralized.
Technical Specifications (Compact)
- Inputs: 8 channels, 10‑30V DC, On‑state current 2.5‑11 mA
- Outputs: 8 channels, 10‑30V DC, current rating (vertical) 500mA @ 60°C, 1A @ 30°C
- External power: 19.2‑30V DC, 300 mA max draw
- Communication: Remote I/O (RIO) via 1771‑CD or Belden 9463 cable
- Baud rates: 57.6K, 115.2K, 230.4K (termination: 150 Ω or 82 Ω)
- LED indicators: Per‑channel status + OK LED
- Mounting: DIN‑rail; vertical or horizontal orientation
- Power dissipation: 11.8 W (41 BTU/hr)
- Wiring: 14 AWG stranded max, 3/64″ insulation
Suitable Equipment & Compatibility
- Allen‑Bradley PLC‑2, PLC‑3, PLC‑5 (1785 series)
- SLC 500 (1747 series), CompactLogix, ControlLogix
- Any RIO‑capable controller using 1771‑CD or Belden 9463 cable
- Works with 1791 series blocks in distributed I/O networks
Why Buy From Oiltech Controls?
- Over 15 years supplying industrial automation spares.
- Global shipping – FedEx, UPS, DHL available.
- Tested surplus / refurbished inventory for obsolete systems.
- 12‑month warranty on every module.
- Every unit verified with technical checks before dispatch.
- Expert support for legacy control system replacements.
Shipping & Warranty
- Dispatch: 24‑28 hours after order confirmation.
- Carriers: FedEx, UPS, DHL – tracked worldwide.
- Warranty: 12 months from invoice date.
5 Professional FAQs
- Q: Can I use this module with ControlLogix without a RIO scanner?
A: No. You need a RIO communication module (e.g., 1756‑DHRIO) to interface with ControlLogix. - Q: What happens if I exceed the output current rating?
A: Internal current protection will activate, but sustained overload may damage the output. Derate according to mounting and temperature. - Q: Which termination resistor should I choose?
A: Use 150 Ω for 57.6K and 115.2K baud; use 82 Ω for 230.4K baud. Connect across terminals 6 (BLU) and 8 (CLR). - Q: Is this module compatible with 24V AC sensors?
A: No. It accepts only 10‑30V DC inputs. AC signals will not be recognized. - Q: Can I mix input and output wiring in the same terminal block?
A: Yes, but group inputs and outputs separately to avoid confusion. Use proper fusing on output circuits.
Selection Guide (Buying Advice)
- Check your controller’s RIO baud rate – match termination resistor accordingly.
- Calculate total output current per channel; consider derating for horizontal mounting.
- If you need more I/O, consider 1791‑16AC or 1791‑32A0 models.