3500/33-01-02 – Bently Nevada 16-Channel Relay Output Module
Full-height module · 16 independent SPDT relays · programmable voting logic · fits 3500 rack
Product Overview
- 3500/33-01-02 provides 16 relay outputs for 3500 rack systems.
- Each output is independently programmable with voting logic (AND/OR).
- Alarm Drive Logic uses alert/danger status, Not-OK, and measured variables from any monitor channel.
- Epoxy-sealed relays with built-in arc suppressor (250 Vrms).
Key Technical Specifications
- Power Consumption: 5.8 W typical
- Relay Type: SPDT (single-pole double-throw)
- Contact Life: 10,000 cycles
- Relay Operation: Four groups of four channels – switch selectable for Normally De-energized (ND) or Normally Energized (NE).
- Environmental Sealing: Epoxy-sealed · arc suppressor installed as standard
Contact Ratings – Standard Systems
- DC (resistive load): Max 5 A · Max 125 Vdc · Max power 70 W @ 24 Vdc, 10 W @ 48 Vdc, 9 W @ 60 Vdc
- AC (resistive load): Max 5 A · Max 250 Vac · Max 1200 VA
- Min switched current: 100 mA @ 5 Vdc
Special Low Current Relay (Gold-plated)
- Min switched current: 1 mA @ 1 Vdc
- Max switched current: 100 mA @ 48 Vdc
- AC up to 120 Vac: Min 1 mA (gold) · Max before damage 5 mA
Physical Dimensions & Rack Space
- Main Module: 241 x 24.4 x 242 mm (9.50 x 0.96 x 9.52 in) · 0.7 kg (1.6 lb) · 1 full-height front slot
- I/O Module: 241 x 24.4 x 99.1 mm (9.50 x 0.96 x 3.90 in) · 0.4 kg (1.0 lb) · 1 full-height rear slot
Front Panel LEDs & Status
- OK LED: Illuminated when module operates properly.
- TX/RX LED: Flashes during communication with other 3500 rack modules.
- CH Alarm LED: Illuminated when relay channel is in alarm state.
Compatible Systems & Applications
- Fits standard 3500 rack – any slot to the right of TDI module.
- Ideal for reciprocating compressors, turbines, and critical rotating machinery.
- Works with Modicon Quantum and other DCS/PLC systems for alarm and shutdown logic.
Oiltech Controls’s Insight
- The 3500/33-01-02 offers flexible voting logic for critical alarm sequences.
- Its ND/NE switchable groups simplify integration with existing safety systems.
- Gold-plated low current option supports sensitive instrumentation circuits.
Professional FAQ – 5 Expert Q&A
- Q: Can I mix ND and NE relays on the same module?
A: Yes. The 16 channels are divided into four groups of four. Each group is switch-selectable for ND or NE operation, giving you flexibility per application. - Q: What is the difference between standard and low current relay versions?
A: Standard relays handle up to 5 A (250 Vac / 125 Vdc). Low current (gold-plated) relays are for sensitive circuits – min 1 mA @ 1 Vdc, max 100 mA @ 48 Vdc. Do not exceed 5 mA for AC gold contacts to avoid damage. - Q: How do I program the voting logic for each relay?
A: Use the 3500 configuration software. Each relay’s Alarm Drive Logic supports AND/OR combinations of alert/danger status, Not-OK, and measured variables from any monitor channel in the rack. - Q: Is this module compatible with existing 3500 racks?
A: Absolutely. The 3500/33-01-02 fits any full-height front slot to the right of the TDI. It communicates via the rack’s backplane – no additional wiring needed. - Q: What should I consider when choosing between 3500/33 and other relay modules?
A: Choose 3500/33 for 16 independent channels with programmable logic. It’s ideal when you need per-channel voting and mixed ND/NE groups. For fewer channels or fixed logic, consider the 3500/32 series. Always verify contact ratings match your load (AC/DC, current, voltage).
Shipping, Warranty & Support
- Shipping: FedEx, UPS, DHL – 24 to 28 hours dispatch after order.
- Warranty: 12 months against defects · technical verification before shipment.
- Inquiries: info@oiltechcontrols.com · +86 158 8020 0923 (WhatsApp)
Why Buy From Oiltech Controls?
- Decades of expertise – over 15 years in industrial automation spares.
- Worldwide delivery – reliable logistics network.
- Quality assured – each unit tested before shipment.
- 12-month coverage – full warranty on all modules.
- Legacy system support – we keep obsolete controls running.
- Technical verification – every order validated by our engineers.
Copyright © 2026 Oiltech Controls Limited. https://www.oiltechcontrols.com/ All rights reserved.










Reviews
There are no reviews yet.