Product Identification
- Manufacturer: GE Fanuc / GE Intelligent Platforms
- Model: IC697MDL640
- Series: Series 90-70
- Type: Discrete Input Module
- Logic: Positive / Negative
Key Specifications
- Rated Voltage: 125 VDC
- Inputs: 16 (4 isolated groups of 4)
- Input Current: 5 mA at rated voltage
- Current Required: 0.3 A
- Input Range: -35 to 145 VDC
- DC Power: Yes
- AC Power: No
- LED Indicators: On/off status per point
Filter & Interrupt Features
- Selectable filter: 1 ms or 10 ms
- One input configurable as interrupt input
- Features depend on GE IC697 PLC usage
Compatibility & Logic Support
- Supports positive and negative logic
- Proximity switch compatible
- Input current-voltage meets IEC standards
- Mechanically keyed – direct replacement for similar modules
Configuration & Programming
- No jumpers or DIP switches required
- Configure via Windows OS or MS-DOS software
- Supports Windows NT or 95
- Connect via SNP port or Ethernet TCP/IP
- Programming device handles software configuration
LED Indicators
- Located on top side of the module
- Show on/off status for each PLC logic point
Signal Flow
- Input device delivers current between module input and power bus
- Positive and negative logic both supported
Installation & Setup
- Insert into Series 90-70 rack – mechanically keyed
- Connect field devices to input terminals
- Select filter time via software configuration
- Configure interrupt input if needed
Certifications
- UL Recognized
- CE Marked
- RoHS Compliant
Package Contents
- IC697MDL640 module ×1
- Installation guide ×1
Warranty & Shipping
- 12-month warranty against defects
- Ships within 24–28 hours after order
- Carriers: FedEx, UPS, DHL
Oiltech Controls Review
“This input module offers flexible logic support for Series 90-70 systems. The selectable filter handles noisy environments. Interrupt input adds real-time response capability.”
Oiltech Controls Insight
“Keep this module as a spare for critical I/O racks. Its 4 isolated groups reduce ground loop issues. Configuration is quick – no hardware jumpers to set.”
Typical Applications
- PLC input racks for industrial automation
- Discrete sensor monitoring (proximity switches)
- Motor control center status inputs
- Conveyor system logic inputs
- Retrofit projects for Series 90-70 systems
Professional FAQ
- What is the difference between 1 ms and 10 ms filter settings?
1 ms gives faster response; 10 ms rejects more electrical noise – choose based on your environment. - Can I use this module with 24 VDC sensors?
No, it requires 125 VDC – check your sensor voltage before connecting. - How do I configure the interrupt input?
Use the software configuration tool – assign one of the 16 inputs as interrupt in the PLC program. - Is this module compatible with Series 90-30 racks?
No, it is designed exclusively for Series 90-70 racks. - What does positive/negative logic mean?
It means the module can accept current sourcing (positive) or sinking (negative) field devices.
Experienced Q&A
- Can I mix logic types on different groups?
Yes, each of the 4 isolated groups can be wired independently for positive or negative logic. - How do I know if the filter is set correctly?
Monitor input response time – if noise causes false triggers, increase to 10 ms. - Does this module support hot-swap?
No, power down the rack before insertion or removal.
Selection Guide
- Confirm your system uses Series 90-70 PLC.
- Verify your field sensors operate at 125 VDC.
- Check if you need interrupt capability – only one channel supports it.
- Select filter time based on your noise environment.
Why Buy From Oiltech Controls?
- Over 15 years in industrial automation spares
- Worldwide shipping – fast and trackable
- Tested surplus and refurbished stock available
- 12-month warranty on every purchase
- Technical verification performed before dispatch
- Expert support for obsolete control systems
Contact us:
info@oiltechcontrols.com |
+86 158 8020 0923
Copyright © 2026 Oiltech Controls Limited. https://www.oiltechcontrols.com/ All rights reserved.