XNX-AMAI-NNNN Pinout and Terminal Block Wiring Diagram
Every Honeywell XNX universal transmitter body — AMAI, AMSV, AMAV variants — uses an identical 10-pin terminal block labeled TB1 through TB4. The only variations are on TB3 (output and digital options) and TB4 (relay and remote reset). This pinout is from XNX Technical Manual Rev. 16 (document SPS-HIS-XNX-TM-16-09-20), page 24.
TB1 — Power Supply
| Pin | Label | Function | Notes |
|---|---|---|---|
| TB1-1 | V+ | Positive supply input (12–24 V DC) | Minimum 12 V DC; use 24 V DC for long cable runs (> 500 m) |
| TB1-2 | V– | Negative supply input / ground | Chassis bond recommended on remote sensors |
| TB1-3 | FG | Frame ground (earth) | Bond to equipment chassis; required for lightning protection |
Supply current: XNX-AMAI-NNNN draws 22 mA quiescent + HART superimposed. Your power supply must deliver 42 mA minimum at 12 V DC.
TB2 — 4-20 mA Analog Output
Two-wire, single-ended, isolated from power supply — this is key for noise immunity.
| Pin | Label | Function | Notes |
|---|---|---|---|
| TB2-1 | mA+ | Positive output of 4-20 mA current source | Connect to PLC AI+ input |
| TB2-2 | mA– | Negative output of 4-20 mA current source | Connect to PLC AI– input |
Important: the 4-20 mA analog loop is separate from the power loop. The XNX does not draw its operating current from the 4-20 mA loop. The PLC analog input must be isolated if TB1 ground is tied to building earth — ground loops corrupt mA readings.
TB3 — HART Communication
Dedicated 2-wire pair — HART is not superimposed on the analog wires on XNX.
| Pin | Label | Function | Notes |
|---|---|---|---|
| TB3-1 | H+ | Positive HART bus wire | 220 Ω terminating resistor mandatory between TB3-1 and TB3-2 |
| TB3-2 | H– | Negative HART bus wire | Connect to HART master’s H– pin |
Mandatory 220 Ω resistor: Honeywell specifies this in Quick Start Guide section 4.4.1. Without it the HART bus appears dead — even though the 4-20 mA analog is healthy. The XNX applies its own bus bias; the 220 Ω forms the low-impedance load required for FSK signaling.
TB4 — Remote Reset (AMAI-NNNN variant)
On AMAI-NNNN (no relay), TB4 is dedicated entirely to the remote fault/alarm reset dry contact:
| Pin | Label | Function | Notes |
|---|---|---|---|
| TB4-1 | RST+ | Reset input contact | Polarity does not matter — dry contact only |
| TB4-2 | RST– | Reset input contact | 200 ms minimum closure clears faults |
| TB4-3 | (unused) | — | On relayed variants, TB4-3 = fault relay NC contact |
| TB4-4 | (unused) | — | On relayed variants, TB4-4 = fault relay common |
Dry contact only — never apply voltage. The XNX generates its own internal bias across TB4. External voltage damages the reset input optocoupler.
Complete Wiring Example
┌─────────────────────────────────────────────┐
│ Honeywell XNX-AMAI-NNNN │
│ │
24 V DC ─────────┤ TB1-1 V+ TB1-2 V– TB1-3 FG ── Chassis │
│ │
PLC AI+ ─────────┤ TB2-1 mA+ TB2-2 mA– ── PLC AI– │
│ │
HART + ──────────┤ TB3-1 H+ TB3-2 H– ── HART – │
│ └── 220 Ω terminating resistor ──┘ │
│ │
PLC DI (reset) ──┤ TB4-1 RST+ TB4-2 RST– ── Dry contact │
│ │
└─────────────────────────────────────────────┘
Cable Selection by Run Length
| Run Length | Cable Type | AWG | Max Loop Resistance |
|---|---|---|---|
| < 50 m | Shielded twisted pair (STP) | 22 AWG | 120 Ω (wire + HART resistor) |
| 50–500 m | Shielded twisted pair | 18 AWG | 120 Ω |
| > 500 m | STP + HART repeater | 16 AWG | Contact Honeywell Applications Engineering |
Grounding rule: shield cable on one end only (XNX TB1-3 FG, not at PLC). Double-ended shielding creates ground loops that inject 50/60 Hz noise into 4-20 mA readings.
Common Wiring Mistakes
| Mistake | Consequence | Fix |
|---|---|---|
| Forget 220 Ω HART resistor | HART master sees dead bus; analog OK | Add resistor between TB3-1 and TB3-2 |
| Ground shield at both ends | 4-20 mA reading ±0.5 % FS 50/60 Hz ripple | Ground at XNX only |
| Apply external voltage to TB4 | Reset optocoupler damages (no field repair) | TB4 is dry contact only |
| AWG smaller than 22 | Loop resistance exceeds 120 Ω; HART drops | Use 22 AWG minimum |
| Cross-connect mA+ to H+ | HART FSK modulates 4-20 mA reading | Correct pinout; separate TB2 and TB3 pairs |
For the complete XNX fault code reference — all 18 F-codes + mA states — jump to our master fault code hub.
Related Guides
- XNX Fault Reset: TB4 Remote Pin and Magnetic Switch — how TB4 clearing actually works
- XNX-AMAI-NNNN Order Code Breakdown — what each part number segment means
Frequently Asked Questions
Can I use a single 2-wire cable for both 4-20 mA analog and HART on XNX-AMAI-NNNN?
No. The XNX-AMAI-NNNN does not support HART superimposed on the analog wires — HART is a dedicated pair on TB3. You need two separate cable pairs: TB2-1/2 for 4-20 mA analog and TB3-1/2 for HART digital, plus TB1-1/2 for 24 V DC power. The newer XNX V series supports HART-on-analog-wire, but AMAI is the older architecture.
My 4-20 mA reading has ±1.0 % FS 50 Hz ripple after wiring — what’s wrong?
This is a ground loop caused by double-ended cable shielding. The XNX TB1-3 FG frame-ground combined with PLC analog input board grounding creates a closed loop through building earth. Shield the cable at one end only — always at the XNX TB1-3 FG terminal, not at the PLC. Once single-ended, the ripple disappears within one power cycle.
Is TB4 polarity-sensitive for remote reset?
No. TB4 is a dry-contact detector with polarity-insensitive inputs — the XNX applies a weak internal bias voltage and senses whether a contact closure shorted the two pins. A relay closing between TB4-1 and TB4-2 works identically regardless of which pole faces which pin. The only requirement is the contact stay closed ≥ 200 ms.