XNX-AMAI-NNNN Part Number: Every Character Decoded
The Honeywell XNX universal transmitter part number follows a fixed 9-character schema of letter groups that tell you exactly what certification, body material, thread type, output, and sensor are in the box. XNX-AMAI-NNNN means aluminum-body, M25-thread, 4-20 mA + HART, no relay / no Modbus / no FF, no local HART port, and no sensor included — it is a transmitter body only.
XNX - A - M - A - I - N - N - N - N
1 2 3 4 5 6 7 8 9
Body Thread I/O Output Relay FF Sensor
Segment-by-Segment Meaning
| Segment | Position | Value | Meaning | Alternatives |
|---|---|---|---|---|
| XNX | 1–3 | Always XNX | Honeywell Universal Transmitter family identifier | — |
| A | 4 | A | Explosion proof body | E = EEx d / IECEx |
| M | 5 | M | Body material | A = aluminum, S = stainless steel 316 |
| A | 6 | A | Thread type | M = M25 × 1.5, G = 3/4″ BSP, N = NPT 3/4″ |
| I | 7 | I | Output option | V = 4-20 mA + HART, R = 3 relays, M = Modbus RTU, F = Foundation Fieldbus |
| N | 8 | N | No relay / no digital option | R = 3 Form-C relays, M = Modbus, F = Foundation Fieldbus |
| N | 9 | N | No local HART port | H = local HART adapter included |
| NNN | 10–12 | NNN | Transmitter body only, no sensor | Replace with sensor code, e.g. CB1 = catalytic bead |
What You Get vs. What You Don’t
Included with XNX-AMAI-NNNN:
- Aluminum die-cast body, rated NEMA 4X / IP65 / ATEX II 2G Ex d IIC T4 Gb (zone 1 certified).
- 4-20 mA analog output + HART v7 communication on the same wire pair.
- Front panel with magnetic switch (no tools required for menu access).
- 12–24 V DC supply range, 22 mA quiescent current.
Not included (you must order separately):
- Sensor head — the NNN tail means no sensor. Order a sensor separately: XNX-00-A00-00-CB1 (catalytic bead), XNX-00-A00-00-NH3 (ammonia EC), XNX-00-A00-00-H2S (H₂S EC), XNX-00-A00-00-CO2 (IR CO₂ 30-series), etc.
- Local HART adapter — order XNX-HART if you need an on-unit HART keypad.
- Relay module — mutually exclusive with Modbus / FF; order as a factory option (XNX-Relay).
- Mounting kit — wall mount: XNX-WALL, pipe mount: XNX-PIPE, duct mount: XNX-DUCT.
Why Choose AMAI over AMSV?
The three aluminum-body variants differ only in material and output:
| Variant | Body | Output | Typical Use Case |
|---|---|---|---|
| XNX-AMAI-NNNN | Aluminum | 4-20 mA + HART | Refineries, petrochemical, offshore platforms |
| XNX-AMSV-NNNN | Stainless steel 316 | 4-20 mA + HART | Marine, coastal, heavy-chloride environments |
| XNX-AMAV-NNNN | Aluminum | 4-20 mA + HART | Same as AMAI; older production — both V and A are current |
For the stainless vs. aluminum corrosion decision framework with salt-spray test data, see our AMSV vs. AMAI vs. AMAV material comparison.
Mutual Exclusion Rule
Do not combine relay option with Modbus or Foundation Fieldbus — Honeywell documents this explicitly in datasheet section 3. If you need 3 relays and digital bus, you must use two separate transmitters or chain the XNX relay output to a third-party digital I/O block.
Loop Resistance Tip
The AMAI transmitter draws 22 mA quiescent current plus HART superimposed signals — total loop current is 22 mA + gas reading. Loop resistance must stay below 120 Ω per Honeywell wiring manual section 4.4.1. For HART specifically, a 220 Ω HART terminating resistor must be installed on TB3 between the HART master and the transmitter.
Related Guides
For the complete XNX fault code reference across all personalities — EC, IR, mV, and catalytic bead — jump to our master fault code hub.
Also check these related guides:
- XNX-AMAI-NNNN Pinout and Terminal Block Wiring Diagram — TB1/TB2/TB3/TB4 full pinout
- XNX INHIBIT 2.0 mA Power-Up Delay Explained — why 2.0 mA appears after power on
- XNX Fault Reset: TB4 Remote Pin and Magnetic Switch — three ways to clear faults
Frequently Asked Questions
Does XNX-AMAI-NNNN include the gas sensor head, or do I order it separately?
The NNN tail in XNX-AMAI-NNNN means transmitter body only, no sensor. You must order the sensor as a separate Honeywell part number: XNX-00-A00-00-CB1 (catalytic bead), XNX-00-A00-00-NH3 (ammonia EC), XNX-00-A00-00-H2S (H₂S EC), XNX-00-A00-00-CO2 (IR CO₂ 30-series). The sensor plugs directly into the J304 connector on the transmitter body — no tools required, field-swappable.
What is the loop resistance limit for XNX-AMAI-NNNN HART communication?
Max loop resistance is 120 Ω per Honeywell XNX wiring manual section 4.4.1. This includes wire resistance plus the mandatory 220 Ω HART terminating resistor on TB3. Without the 220 Ω resistor the HART master sees a flat-bus and cannot communicate even if the 4-20 mA analog signal is healthy.
Can I field-upgrade XNX-AMAI-NNNN from 4-20 mA to Modbus or Foundation Fieldbus?
No. The 7th character (I for 4-20 mA + HART, R for relays, M for Modbus, F for FF) is a hardware configuration, not a software setting. You cannot field-swap the output board — you must order the correct variant from the start. However, relay modules (segment 8) can be added or removed in the field as they are external modules.