XNX-AMAI-NNNN Part Number: Every Character Decoded

The Honeywell XNX universal transmitter part number follows a fixed 9-character schema of letter groups that tell you exactly what certification, body material, thread type, output, and sensor are in the box. XNX-AMAI-NNNN means aluminum-body, M25-thread, 4-20 mA + HART, no relay / no Modbus / no FF, no local HART port, and no sensor included — it is a transmitter body only.

XNX - A - M - A - I - N - N - N - N
 1   2   3   4   5   6   7   8   9
    Body Thread I/O Output Relay FF Sensor

Segment-by-Segment Meaning

Segment Position Value Meaning Alternatives
XNX 1–3 Always XNX Honeywell Universal Transmitter family identifier —
A 4 A Explosion proof body E = EEx d / IECEx
M 5 M Body material A = aluminum, S = stainless steel 316
A 6 A Thread type M = M25 × 1.5, G = 3/4″ BSP, N = NPT 3/4″
I 7 I Output option V = 4-20 mA + HART, R = 3 relays, M = Modbus RTU, F = Foundation Fieldbus
N 8 N No relay / no digital option R = 3 Form-C relays, M = Modbus, F = Foundation Fieldbus
N 9 N No local HART port H = local HART adapter included
NNN 10–12 NNN Transmitter body only, no sensor Replace with sensor code, e.g. CB1 = catalytic bead

What You Get vs. What You Don’t

Included with XNX-AMAI-NNNN:

  • Aluminum die-cast body, rated NEMA 4X / IP65 / ATEX II 2G Ex d IIC T4 Gb (zone 1 certified).
  • 4-20 mA analog output + HART v7 communication on the same wire pair.
  • Front panel with magnetic switch (no tools required for menu access).
  • 12–24 V DC supply range, 22 mA quiescent current.

Not included (you must order separately):

  1. Sensor head — the NNN tail means no sensor. Order a sensor separately: XNX-00-A00-00-CB1 (catalytic bead), XNX-00-A00-00-NH3 (ammonia EC), XNX-00-A00-00-H2S (H₂S EC), XNX-00-A00-00-CO2 (IR CO₂ 30-series), etc.
  2. Local HART adapter — order XNX-HART if you need an on-unit HART keypad.
  3. Relay module — mutually exclusive with Modbus / FF; order as a factory option (XNX-Relay).
  4. Mounting kit — wall mount: XNX-WALL, pipe mount: XNX-PIPE, duct mount: XNX-DUCT.

Why Choose AMAI over AMSV?

The three aluminum-body variants differ only in material and output:

Variant Body Output Typical Use Case
XNX-AMAI-NNNN Aluminum 4-20 mA + HART Refineries, petrochemical, offshore platforms
XNX-AMSV-NNNN Stainless steel 316 4-20 mA + HART Marine, coastal, heavy-chloride environments
XNX-AMAV-NNNN Aluminum 4-20 mA + HART Same as AMAI; older production — both V and A are current

For the stainless vs. aluminum corrosion decision framework with salt-spray test data, see our AMSV vs. AMAI vs. AMAV material comparison.

Mutual Exclusion Rule

Do not combine relay option with Modbus or Foundation Fieldbus — Honeywell documents this explicitly in datasheet section 3. If you need 3 relays and digital bus, you must use two separate transmitters or chain the XNX relay output to a third-party digital I/O block.

Loop Resistance Tip

The AMAI transmitter draws 22 mA quiescent current plus HART superimposed signals — total loop current is 22 mA + gas reading. Loop resistance must stay below 120 Ω per Honeywell wiring manual section 4.4.1. For HART specifically, a 220 Ω HART terminating resistor must be installed on TB3 between the HART master and the transmitter.

Related Guides

For the complete XNX fault code reference across all personalities — EC, IR, mV, and catalytic bead — jump to our master fault code hub.

Also check these related guides:


Frequently Asked Questions

Does XNX-AMAI-NNNN include the gas sensor head, or do I order it separately?

The NNN tail in XNX-AMAI-NNNN means transmitter body only, no sensor. You must order the sensor as a separate Honeywell part number: XNX-00-A00-00-CB1 (catalytic bead), XNX-00-A00-00-NH3 (ammonia EC), XNX-00-A00-00-H2S (H₂S EC), XNX-00-A00-00-CO2 (IR CO₂ 30-series). The sensor plugs directly into the J304 connector on the transmitter body — no tools required, field-swappable.

What is the loop resistance limit for XNX-AMAI-NNNN HART communication?

Max loop resistance is 120 Ω per Honeywell XNX wiring manual section 4.4.1. This includes wire resistance plus the mandatory 220 Ω HART terminating resistor on TB3. Without the 220 Ω resistor the HART master sees a flat-bus and cannot communicate even if the 4-20 mA analog signal is healthy.

Can I field-upgrade XNX-AMAI-NNNN from 4-20 mA to Modbus or Foundation Fieldbus?

No. The 7th character (I for 4-20 mA + HART, R for relays, M for Modbus, F for FF) is a hardware configuration, not a software setting. You cannot field-swap the output board — you must order the correct variant from the start. However, relay modules (segment 8) can be added or removed in the field as they are external modules.