XNX Fault and Alarm Reset: Front-Panel Magnet, TB4 Remote Pin, and HART Command

When your Honeywell XNX is in 1.0 mA fault state or has an alarm latched, you need to clear it before the transmitter resumes normal operation. The XNX family gives you three independent reset methods depending on whether you have physical access, a local HART master, or a PLC digital input.

Method 1: Front-Panel Magnetic Switch

Slide a ferrite magnet across the RESET zone on the XNX front panel while the fault displays. The fault icon disappears; mA transitions to WARM-UP (2.0 mA) or live gas (4–20 mA). Do not use neodymium magnets — their field saturates the magnetometer chip inside the panel.

Method 2: TB4 Remote Reset Pin

Every XNX has TB4 terminal block on the side of the enclosure. The two dedicated reset pins work as a dry-contact detector — polarity does not matter.

Pin Function Duration
TB4-1 Reset input contact Minimum 200 ms closure
TB4-2 Reset input contact (opposite side) Minimum 200 ms closure

To reset: momentarily close a dry contact (relay output, switch, PLC DI) between TB4-1 and TB4-2. The XNX debounces the input — contacts shorter than 200 ms are ignored. Never apply external voltage to TB4 — the XNX generates its own bias; external voltage will damage the reset input optocoupler.

TB number variation: some XNX variants mark reset as TB5 instead of TB4 — confirm on your transmitter’s own terminal diagram.

Method 3: HART Software Reset

If you have a HART master connected via the 220 Ω terminating resistor on TB3, send HART Universal Command 93 — Write Fault Code Clear. This clears all latched faults in one message without touching the transmitter. Use Command 94 (Write Alarm Code Clear) to clear alarm latches independently.

Reset Safety Rules

  • Always fix the root cause first. Resetting F-127 (calibration lost) without recalibrating will clear the fault but the transmitter reads garbage until new calibration constants are written.
  • Clear highest-numbered faults first (F-127 → F-126 → F-50 → F-40 → F-30 → F-20 → F-10). Lower-numbered codes often clear themselves when root cause is removed. See our complete fault code table.
  • TB4 is dry contact only. External voltage damages the optocoupler.

Post-Reset Verification

After any reset: (1) fault icon gone from front panel, (2) mA no longer 1.0 or 3.0 mA, (3) fault relay de-energizes, (4) HART Command 120 reads “0 new faults”.

If a fault re-appears within 24 hours, you have a hardware fault (leaking sensor cell, intermittent cable connection) — reset alone won’t fix it.

Wiring Diagram for TB4 Integration

PLC Digital Output        XNX TB4-1      XNX TB4-2
     │                      │                │
     └─────────── relay ────┴────────────────┘
                 NO / NC dry contact

Related Guides


Frequently Asked Questions

TB4 remote reset doesn’t clear the fault — relay pulses but mA stays at 1.0 mA. What’s wrong?

Three likely causes: (1) contact is closing for less than 200 ms — XNX debounces short pulses; slow down your PLC output, (2) you are resetting while the underlying fault condition still exists (e.g., BEAM BLOCKED obstruction still in place) — reset only clears the latch, not the physical fault, (3) Wrong terminal block — some XNX variants mark reset as TB5 instead of TB4; check your transmitter’s own diagram, not a generic one.

Can I reset XNX faults from the HART modem connected to my PC?

Yes, via HART Universal Command 93 (Write Fault Code Clear) and optionally Command 94 (Write Alarm Code Clear). Commands 93 and 94 are fully universal and work on every XNX model. You need the 220 Ω HART terminating resistor on TB3, a HART modem (USB or Bluetooth), and HART master software (FieldMate, AMS, Honeywell’s own configuration utility).

Is front-panel magnetic switch reset safe for ATEX Zone 1 classified areas?

Yes. Honeywell explicitly states in Safety Manual section 7.1 that the magnet zone is non-incendive (Ex n) rated and accessible from the outside of the explosion-proof enclosure. You do not need to open the lid or require a hot-work permit. Use ferrite magnet only — neodymium damages the magnetometer chip.