Product Overview
- IS215VPROH1BD – Emergency Turbine Protection Module for GE Mark VI.
- Provides triple redundant overspeed protection.
- Operates independently from the main turbine control system.
- Controls trip solenoids through TREG terminal board.
- Input: 125 V dc (70-145 V dc). Output: 5 V dc and 28 V dc.
Technical Specifications
- Brand: General Electric
- Model: IS215VPROH1BD
- Series: Mark VI
- Type: Emergency Turbine Protection Board (VPRO)
- Frame Rate: Up to 100 Hz
- MPU Pulse Rate: 2 Hz to 20 kHz
- Input Supply: 125 V dc (70-145 V dc)
- Output: 5 V dc and 28 V dc
- MPU Output Voltage: 150 V p-p @ 60 KΩ load
- Max Short Circuit Current: 100 mA
- MPU Output Resistance: 200 Ω with 85 mH inductance
Protection System Architecture
- Triple redundant VPRO boards in a separate protection module.
- Works with TPRO and TREG terminal boards.
- Controls up to 3 trip solenoids.
- TREG provides 125 V dc positive side to solenoids.
- TRPG provides negative side for complete circuit.
- Either board can initiate a turbine trip.
Relay Voting Mechanism
- Controls 12 relays on TREG terminal board.
- 9 relays organized into 3 groups of 3.
- Forms a voting mechanism for trip decisions.
- Requires consensus before initiating critical actions.
- Enhances reliability and prevents false trips.
MPU Characteristics & Signal Conditioning
- Output resistance: 200 Ω with 85 mH inductance.
- Output voltage: 150 V p-p at 60 KΩ load.
- Energy is insufficient to generate a spark – safe operation.
- Max short circuit current limited to 100 mA.
- Normal mode load of 400 Ω reduces input voltage.
- Prevents overvoltage on downstream components.
Ethernet & System Integration
- Features Ethernet connection for IONet communications.
- Enables data exchange with control modules.
- Enhances monitoring and management capabilities.
- Integrates with broader Mark VI control network.
Installation & Cabling
- Proper cabling between TPRO, TREG, and VPRO is critical.
- Ensures seamless communication and coordination.
- Enables timely response to emergency situations.
- Follow GE wiring diagrams for correct connections.
Oiltech Controls Review
- Reliability: Triple redundant design ensures maximum turbine safety.
- Performance: Fast 100 Hz frame rate for real-time protection.
- Integration: Ethernet IONet simplifies system connectivity.
- Value: Critical safety component for Mark VI turbines.
Oiltech Controls’s Insight
- This VPRO board is the last line of defense for turbine overspeed.
- Always test MPU output voltage before installation.
- Verify the voting relay configuration matches your application.
- Keep spare VPRO boards to minimize turbine downtime.
- Common issue – check cabling between TPRO/TREG and VPRO.
Compatible Systems & Applications
- Systems: GE Mark VI, Speedtronic™ turbine control.
- Applications: Gas turbine overspeed protection, steam turbine emergency trip.
- Works with TPRO and TREG terminal boards.
- Used in power generation, oil & gas, and industrial facilities.
Why Buy From Oiltech Controls?
- 15+ years in industrial automation spares.
- Global shipping with reliable logistics.
- All items tested before shipment.
- Surplus and refurbished options available.
- 12-month warranty on every product.
- Expert support for obsolete control systems.
Warranty & Shipping
- 12-month warranty against defects.
- Ships within 24-28 hours of order.
- Express via FedEx, UPS, or DHL.
- Tracking provided upon shipment.
Professional FAQ
- Q: What is the input voltage range for this board?
- A: Accepts 125 V dc with operating range of 70-145 V dc.
- Q: How does the voting mechanism work?
- A: 9 relays in 3 groups of 3 – requires consensus to trip.
- Q: Can this board connect to IONet?
- A: Yes, it has Ethernet for IONet communications.
- Q: What is the maximum MPU pulse rate?
- A: Supports 2 Hz to 20 kHz pulse rate range.
- Q: Is this board redundant?
- A: Yes, the system uses triple redundant VPRO boards.
Experience-based Buying Guide
- Confirm your turbine uses Mark VI control system.
- Check if you have TPRO and TREG terminal boards.
- Verify MPU output voltage matches your sensors.
- Test all relay groups before commissioning.
- Stock spare boards for critical turbine protection.
For inquiries:
info@oiltechcontrols.com |
+86 158 8020 0923
Copyright © 2026 Oiltech Controls Limited. https://www.oiltechcontrols.com/ All rights reserved.










Reviews
There are no reviews yet.