TM3AQ4 Schneider Electric Modicon TM3 Analog Output Module
The TM3AQ4 is a 4-channel analog output module from the Schneider Electric Modicon TM3 range. It delivers 12-bit voltage or current outputs. Each channel is software configurable, so one card covers 0-10 V, ±10 V, 0-20 mA, and 4-20 mA loops. Isolation sits at 1500 V AC between output and supply. The module draws 50 mA at 5 V DC and 80 mA at 24 V DC under full load. It fits Modicon M221, M241, M251, and M262 controllers. A removable 5.08 mm screw terminal block speeds up wiring. The compact 90 × 23.6 × 70 mm housing saves panel space. This module suits machine builders who need mixed signal types on one platform.
Technical Data
- Brand: Schneider Electric
- Model: TM3AQ4
- Series: Modicon TM3
- Module type: Analog output, voltage or current per channel
- Channels: 4
- Signal type: 0-10 Vdc, ±10 Vdc, 0-20 mA, 4-20 mA
- Range: 0-10 V / ±10 V / 0-20 mA / 4-20 mA
- Resolution: 12 bits
- Accuracy: ±0.2% of full scale at 25 °C, ±1% FS over temperature
- Isolation: 1500 V AC output to supply, 500 V AC output to logic
- Diagnostics: Module status, bus status
- Response time: 1 ms conversion + 1 ms per channel + 1 controller cycle; 1 ms stabilization
- Wiring: Removable screw terminal block, 5.08 mm pitch
- Supply voltage: 24 Vdc via TM3 bus
- Bus current: 50 mA at 5 V DC, 80 mA at 24 V DC, full load
- Operating temperature: 0 to +55 °C
- Storage temperature: -25 to +70 °C
- Protection rating: IP20
- Dimensions: 90 × 23.6 × 70 mm
- Weight: 0.115 kg
- Compatible platforms: Modicon M221, M241, M251, M262
- Lifecycle: Active, last verified 2026-09
Oiltech Controls’s Insight
- The TM3AQ4 solves a common panel problem: mixed actuator loops on one card.
- You set voltage or current per channel in software, so no hardware jumpers are needed.
- This cuts spare part count and simplifies stock for maintenance teams.
- The 12-bit resolution fits valve positioners, VFD references, and analog meters.
- Isolation protects the PLC from field transients on long cable runs.
- It is a practical choice for retrofits where panel space is tight.
Where It Fits
- Modicon M221 compact controllers
- Modicon M241 logic controllers
- Modicon M251 distributed controllers
- Modicon M262 motion and IoT controllers
- TM3 expansion racks on the above platforms
- Retrofit panels replacing older analog output cards
Ordering, Shipping, and Warranty
- All units carry a 12 month warranty from the ship date.
- Stock items ship within 24 to 28 hours after payment clears.
- We use FedEx, UPS, and DHL for worldwide delivery.
- Tracking numbers go out with every dispatch notice.
- Each module passes a technical check before packing.
Why Buy From Oiltech Controls?
- Over 15 years supplying industrial automation spare parts
- Shipping support to customers worldwide
- Tested surplus and refurbished units available
- 12 month warranty on every order
- Technical verification completed before shipment
- Backing for obsolete and legacy control systems
Reach us at info@oiltechcontrols.com or message +86 158 8020 0923 on WhatsApp for stock, lead time, and pricing.
FAQ
Q: Can I mix voltage and current outputs on one TM3AQ4?
A: Yes. You configure each channel in software. One channel can drive a 0-10 V valve, while another runs a 4-20 mA transmitter. This saves rack slots and spare parts.
Q: How do I know if the output is drifting over temperature?
A: Watch the ±1% full scale figure over temperature. In practice, check the reading at cold start and after the cabinet warms up. If drift matters, calibrate the loop after 30 minutes of run time.
Q: Does the TM3AQ4 need a separate power supply?
A: No. It draws 24 Vdc through the TM3 bus. It pulls 50 mA at 5 V DC and 80 mA at 24 V DC at full load. Check your bus power budget before you add more modules.
Q: What wiring should I use for 4-20 mA loops?
A: Use shielded twisted pair. Ground the shield at the panel end only. The 1500 V AC isolation helps, but good shielding still matters on long runs near drives. Keep the 5.08 mm terminal block screws tight.
Q: How fast does the output respond after a command change?
A: Budget 1 ms for conversion, 1 ms per channel, plus one controller cycle. Add 1 ms for stabilization. For most valve and VFD reference loops, this is more than fast enough. High-speed test rigs may need a faster card.
Copyright © 2026 Oiltech Controls Limited. https://www.oiltechcontrols.com/ All rights reserved.